Home Private Messages Search
    Products

Pac-Rat
Sleds
Fiberglass Products

  • Resins
  • Gel Coats
  • Fabrics
  • Accessories
  • Castings
  • Epoxy
  • Plastics
  • Urethane Foams
  • DivinyCell
Shelters
  • Spec Data
    1. Radio Shelter
    2. Standard Shelter
  • Pricing
  • Drawings
  • Engineering Data
  • Quality Control Procedures
  • Materials Used
    1. Polar
    2. Plexus
    3. Polyfoam
    4. MAT/Gel Coat
  •     Company
    · Home
    · Contact Us
    · Dealer Pricing
    · FAQ
    · Forums
    · How To Order
    · Plaschem Pictures
    · Private Messages
    · Search
    · Web Links
    WAGNER ENGINEERING

     

                WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     


    By: JWW         Date: 8-11-04                                                                          Page 1 of 21

     

     


    Project: 9 ft. high x 10 ft. wide x 24 ft. lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

    Seismic and wind loads were based on the following from the 2000 I.B.C.

     

    Seismic

     

    Seismic base shear (V) = 1.2 x Sds x W/R ~ Eq. 16-49

     

    V = lateral load applied

    W = total dead load plus 20% snow load. ~ 1617.5.1(4)

    Seismic Use Group I ~ 1616.2

    Seismic Design Category D ~ 1616.3

    Ss=1.5~Max. per 1616.6.3

    Fa =1.0-Table 1615.1.2(1)

    Sds =1.5

    R=6.5

     

    V = .277W

     

    Wind Loads

     

    Use exposure D

    Vel. = 130 mph 3 Sec. Gust ~ IBC Figure 1609

     

    P = Hp x Ec x Iw ~ I.B.C. 1609.6.2.1 ~ Pg.311

     

    Hp (Horiz. Pressure) = 37.1 ~ Table 1609.6.2.1 (1)

    EC (Ht. & Exp. Factor) = 1.47 ~ Table 1609.6.2.1(4)

    IW (Importance Factor ) = .77 ~ Table 1604.5

     

    P = 37.1 x 1.47 x .77 = 42 psf

     

    Snow Load = 160 psf ~ IBC Table 1608.2

    Floor Live Load = 300 psf


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 8-11-04                                                              Page 2 of 21

     

    Project: 9 ft. high x 10 ft. wide x 24 ft. lg. std. Bldg.

     

     

    Summary Of Calculations

     

    Page 5 - Floor

    Max. Horiz. Shear = 21.8 psi – Satisfactory

    Allowable = 50 psi

     

    Page 6 - Floor with 300 psf load

    Max. Fiberglass Stress = 987 psi – Satisfactory

    Max. Wood Stress = 966 psi – Satisfactory

    Def. = .176" < .40" Allowable Def. – Satisfactory

     

    Page 10 - Roof at center of span

    Max. Horiz. Shear = 18.3 psi – Satisfactory

    Allowable = 50 psi

     

    Page 11 - Roof at center of span with 160 psf snow load.

    Max. Fiberglass Stress = 2583 psi – Satisfactory

    Max. Wood Stress = 989 psi – Satisfactory

    Def. = .36" < .48" Allowable Def. – Satisfactory

     

    Page 13 - Roof at ¼ span.

    Max. Fiberglass Stress = 2205 psi - Satisfactory

    Max. Wood Stress = 896 psi - Satisfactory

    Def. = .337" < .483" Allowable Def. - Satisfactory

     

    Page 14 - Roof at end.

    Max. Horiz. Shear = 33.9 psi – Satisfactory

    Allowable = 50 psi


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 8-11-04                                                              Page 3 of 21

     

    Project: 9 ft. high x 10 ft. wide x 24 ft. lg. std. bldg.

     

    Summary Of Calculations Cont.

     

    Page 18 - Side Wall

    Max. Horiz. Shear = 3.7 psi – Satisfactory

    Allowable = 50 psi

     

    Page 19 - Side Wall stress with wind load.

    Max. Fiberglass Stress = 2916 psi – Satisfactory

    Max. Wood Stress = 1140 psi - Satisfactory

     

    Page 20 - Side Wall stress with seismic loading

    Max. Fiberglass Bending Stress = 1745 psi – Satisfactory

    Max. Wood Stress = 682 psi – Satisfactory

    Max. Comp. Stress = 40 psi - Satisfactory

     

    Page 21 - Overturning and Anchor Bolts.

    Safety factor against overturning (without anchor bolts) = 0.6 - Unsatisfactory.

    A minimum of (4) – ½” dia. anchor bolts are required at each side of skid to provide a minimum safety factor of 2. Anchor bolts to have a minimum embed of 3 ½” in concrete or equiv. earth anchor. Building to also have a minimum of (4) – ½" dia. bolts each side of skid.


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: WW                       Date: 8/11/2004                                                           Page 4 of 21

    Project:     9ft. high x 10ft. wide x 24ft. lg. std. bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

    Typical Section Thru Floor





     

     


    a ~ 1.5 Oz. Per Sq. Ft. Fiberglass     <     Tensile Strength =     35,200              E= 2,000,000

    b ~ 1.5 Oz. Per Sq. Ft. Fiberglass     <     Tensile Strength =     35,200             E= 2,000,000

          Comp. Strength =   31,300

    c ~ T & G Plywood   >   Allow. Stress = Min. 1400 p.s.i.    U.B.C. 2- 295    E= 1,800,000

    d ~ T & G Plywood   >   Allow. Stress = Min. 1400 p.s.i.    U.B.C. 2- 295    E= 1,800,000

    e ~ 2 x 4 Wood Studs At 16" O.C.

    f ~ H40 Insulation Core            >        Shear Strength = 50 P.S.I.                        E= 1650


     

     

     

     

     

     

     

     

     

     

     

     

     

     

    std04


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jvvagner@alliancelink.com

     

     

    By:JWW                      Date: 811/2004                                                            Page 5 of 21

    Project:  9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

    Composite Section At Stud ~ Neglecting Insulation


               

     

               


     

    Outside Fiberglass Thickness (A)          0.0625

    Floor Fiberglass Thickness        (B)       0.0625

    O/O Plywood                           (C)         5.375

    Bott. Plywood Thickness          (D)           0.75

    Floor Plywood Thickness         (E)         1.125

    Stud Depth                               (F)            3.5

    Stud Thickness             (G)             1.5

    Width of Section                       (H)              12

    Total Depth                              (M)            5.5

    Vertical Shear Load                                 1653

     

     


    Properties ~ Converting To Composite Section

    n = 1.111111               Effective Width (K) =  13

    (a) area =   0.833333   (b)area =   0.833333   (c) area =  13.5
    (d) area =   9                (e) area =   5.25           total area = 29.41667


     


    Base to C.G.      (N)     2.984

    Floor to C.G.     (P)      2.516                                       14.33333

    Moment of Inertia         119.980                                   1.328

    Sect. Mod. Inside         47.691

    Sect. Mod. Outside      40.204

    Horizon Shear at Insul.21.858 P.S.I.   <    50 P.S.I.    O.K.

     

     

     

     


    std04


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 811/2004                                                            Page 6 of 21

    Project:     9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

    FLOOR BEAM - Stress And Deflection At Center Span With Uniform Load

    WL/8 ~ Supported both ends

     

    Beam Used - See pages 4 & 5

    Sxx =        40.2

    Ixx =         120.0

    Fiberglass min. strength       =                31,300

    Span =             96 " =  8 Ft.      (Skid Span)

    Allow. Def. = Span /    240                   0.40"

     

    Live Load =     3,200               ~ 300 P.S.F. x 8' x 1.33'

    Dead Load =       106               ~ 10   P.S.F. x 8' x 1.33'

    Total Load =    3306

     

    Fiberglass Stress =       987 P.S.I.

    SF =                            32 O.K.

    Wood Stress = 966 P.S.I. < 1400 P.S.I. -O.K.

     

    Def.    =           0.176"              <.40 ~ O.K.

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    std04


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva , Oh 44657

    Ph / Fax ( 330 ) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 8/11/2004                                                           Page 7 of 21

    Project:     9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

    Composite Section Between Studs ~ Neglecting Insulation and Stud


     

                           

     

     

    Outside Fiberglass Thickness    (A)       0.0625

    Floor Fiberglass Thickness        (B)       0.0625

    O/O Plywood                                       (C)         5.375

    Bott. Plywood Thickness.                     (D)           0.75

    Floor Plywood Thk.                             (E)         1.125

    Stud Depth                                           (F)             3.5

    Stud Thickness                         (G)               0

    Width of Section                                   (H)              12

    Total Depth                                          (M)           5.5

    Vertical Shear Load                                              207

     


     


    Properties ~ Converting To Composite Section

    n= 1.111111                Effective Width (K)= 13

    (a) area =   0.833333   (b) area =   0.833333   (c) area =         13.5
    (d)area =   9                   (e) area =   0                  total area = 24.16667


     


    Base to C.G.                (N)         3.076

    Floor to C.G.               (P)         2.424                         14.33333

    Moment of Inertia                   118.843                         1.237

    Sect. Mod. Inside                     49.025

    Sect. Mod. Outside                  38.637

    Horiz. Shear at Insul.    2.573 P.S.I  <  50 P.S.I.     O.K.

     

     

     

     

    std07


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By:JWW                      Date: 8/11/2004                                                           Page 8 of 21

    Project:     9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

    FLOOR BEAM - Stress And Deflection Between Studs With Uniform Load

    WL/8 ~ Supported both ends

     

    Beam Used - See page 7

    Sxx =     38.6

    Ixx =    119.0

    Fiberglass min. strength = 31,300

    Span = 16”

    Allow. Def. = Span /    240             0.07"

     

    Live Load         =         400                  ~ 300 P.S.F. x 1.333' x 1'

    Dead Load       =           13                      ~ 8 P.S.F. x 1.333' x 1'

    Total Load       =          413

     

    Fiberglass Stress           =          21 P.S.I.

    SF        =          1,463 O.K.

    Wood Stress    =          28 P.S.I.          <          1400 P.S.I. ~ O.K.

     

    Def.      =          0.000"              <          .07 ~ O.K.

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    std07


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date:     8/11/2004                                                       Page 9 of 21

    Project:     9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer:  Plaschem Supply & Consulting Inc.


     


    Typical Section Thru Roof


     

               


     


     


    a ~ 1.5 Oz. Per Sq. Ft. Fiberglass  >  Tensile Strength =           35,200          E = 2,000,000

    b ~ 1.5 Oz. Per Sq. Ft. Fiberglass  >  Tensile Strength =           35,200          E = 2,000,000                                                                 Comp. Strength  =        31,300

    c ~ Plywood   >   >   Allow. Stress = Min. 1400 p.s.i.   U.B.C.  2- 295      E = 1,800,000

    d ~ 2.0 Lb./Cu. ft. Urethane Foam   >  Shear Strength  =          50 p.s.i.         E = 1885

    e ~ 3.5" Deep Metal Stud                   > Yield Strength   =        33,000 p.s.i.  E = 29000000

    at 24" c/c                                              Wt. =   0.74 lbs/ft

    Gross Area =   0.219 sq. in.

       Net Area =    0.167 sq. in.

    Ixx =    0.403 in. 4

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    std09


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: WW           Date: 8/11/2004                                                                       Page 10 of 21

    Project:     9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

     


    Roof Composite Section At Stud ~ Neglecting Insulation

    Section At Center

     

               

     

     


    Inside Fiberglass Thickness                   (A)         0.125

    Outside Fiberglass Thickness                (B)       0.1875

    Inside / Inside Wall                   (C)             7.5     < Note:  Dim. Curves From 4 1/2" At The End

    Stud Depth                                           (D)             3.5                   To 7 1/2" At The Center

    Plywood Thickness                   (E)             0.5

    Width of Section                                   (F)              12

    Total Depth                              (M)      7.8125

    Vertical Shear Load                                             1644

     


     


    Properties ~ Converting To Composite Section

    (a & b) n = 1.111         (e) n = 16.111              Effective Width (G) = 13.333

    (a) area =   1.6667       (b) area =   2.5000       (c) area =   6

     (e) area =   2.6906                        total area = 12.8572


     


    Outside to C.G.            (H)       5.650

    Inside to C.G.               (K)       2.163

    Moment of Inertia                     104.225

    Sect. Mod. Inside                     48.191

    Sect. Mod. Outside                  18.448

    Horiz. Shear at Insul.                (Inside) 18.6 P.S.I.     <     50 P.S.I.    O.K.

    Horiz. Shear at Insul.                (Outside)          18.3 P.S.I.     <     50 P.S.I.    O.K.


     

     

    std09


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 8/11/2004                                                           Page 11 of 21

    Project:  9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

     

    ROOF BEAM - Stress And Deflection At Center Span With Uniform Load

     

    Beam Used - See page 9 & 10

    Sxx =        18.45         Outside

    Sxx =        48.19          Inside

    Ixx =         104.0

    Fiberglass min. strength       =                31,300

     

     

    Span =             116 " = 9.67 ft.

     

    Allow. Def. = Span /    240                   0.48 "

     

    Live Load         =          3,094

    Dead Load       =             193

    Total Load       =         3,287

     

    Fiberglass Stress =       2,583 P.S.I.

    SF =                12 O.K.

    Wood Stress    =          989 P.S.I.         <1400 P.S.I. O.K.

    Def.    =           0.357 "       =        .48 O.K.

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    std09


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 8/11/2004                                                           Page 12 of 21

    Project:     9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

     


    Roof Composite Section At Stud ~ Neglecting Insulation

    Section At 1/4 Span

     

               

     


    Inside Fiberglass Thickness                   (A)         0.125

    Outside Fiberglass Thickness                (B)       0.1875

    Inside / Inside Wall                   (C)             6.5     < Note:    Dim. Curves From 4 1/2" At The End

    Stud Depth                              (D)             3.5                     To 7 1/2" At The Center

    Plywood Thickness                   (E)             0.5

    Width of Section                                   (F)              12

    Total Depth                                          (M)      6.8125

    Vertical Shear Load                                             1644

     


     


    Properties ~ Converting To Composite Section
    (a&b) n = 1.111                       (e) n = 16.111                          Effective Width (G) = 13.333

    (a) area =   1.6667       (b) area =   2.5000  (c) area =   6                                            

     (e) area =   2.6906                  total area = 12.8572


     

     

    Outside to C.G.             (H)                  4.844

    Inside to C.G.                (K)                  1.968

    Moment of Inertia                                 78.550

    Sect. Mod. Inside                                 39.908

    Sect. Mod. Outside                              16.215

    Horiz. Shear at Insul.                (Inside) 22.1 P.S.I. <     50 P.S.I.    O.K.

    Horiz. Shear at Insul.                (Outside)          20.7 P.S.I. <     50 P.S.I.    O.K.

     

     

    std12


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 8/11/2004                                                           Page 13 of 21

    Project:     9Ft. High x 10 Ft. Wide x 24 Ft.Lg.Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

     

    Roof Stress and Deflection At 36" (1/4 Span) With Uniform Load

     

    Beam Used - See Page 12

    Sxx = 16.215      Outside

    Sxx = 39.908       Inside

                Ixx = 78.55
    Fiberglass min. strength =          31,300

     

    Span    =          116 "    =         9.67ft.              ¼ span             =          29

    Allow. Def. = Span /   240        =          0.483"

     

    Live Load         =          3094

    Dead Load       =            193

    Total Load       =          3287    w = 28.336

     

    Stress   =          2,205 P.S.I.     O.K.

    SF        =          14 O.K.

     

    Wood Stress    =          896 < 1400 P.S.I. O.K.

     

    Def.    =           0.337 " < .483"     O.K.

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    std12


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 8/11/2004                                                           Page 14 of 21

    Project:     9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.


     


    Roof Composite Section At Stud ~ Neglecting Insulation Section At End


    Section at End

     

               


     


    Inside Fiberglass Thickness                   (A)         0.125

    Outside Fiberglass Thickness                (B)       0.1875

    Inside / Inside Wall                   (C)             4.5      < Note:    Dim. Curves From 4 1/2" At The End

    Stud Depth                              (D)             3.5                      To 7 1/2" At The Center

    Plywood Thickness                   (E)             0.5

    Width of Section                       (F)              12

    Total Depth                             (M)      4.8125

    Vertical Shear Load                                             1644

     


     


    Properties ~ Converting To Composite Section      

    (a & b) n = 1.111         (e) n = 16.111              Effective Width (G) = 13.333

    (a) area =   1.6667       (b) area =   2.5000       (c) area =   6

     (e) area =   2.6906                        total area = 12.8572

     

     

    Outside to C.G.             (H)                  3.233

    Inside to C.G.                (K)                  1.579

    Moment of Inertia                                 39.283

    Sect. Mod. Inside                                 24.872

    Sect. Mod. Outside                              12.150

    Horiz. Shear at Insul.    (Inside) 33.9 P.S.I.   <   50 P.S.I.    O.K.

    Horiz. Shear at Insul.    (Outside)          27.4 P.S.I.   <   50 P.S.I.    O.K.


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 8/11/2004                                                           Page 15 of 21

    Project:     9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     


     

    Roof Composite Section Between Studs ~ Neglecting Insulation & Studs

    Section At End

     

               

     


    Inside Fiberglass Thickness                   (A)         0.125

    Outside Fiberglass Thickness                (B)       0.1875

    Inside / Inside Wall                   (C)             4.5      < Note:    Dim. Curves From 4 1/2" At The End

    Stud Depth                              (D)             3.5                      To 7 1/2" At The Center

    Plywood Thickness                   (E)             0.5

    Width of Section                       (F)              12

    Total Depth                             (M)      4.8125

    Vertical Shear Load                                               170

     


     


    Properties ~ Converting To Composite Section      

    (a & b) n = 1.111         (e) n = 16.111              Effective Width (G) = 13.333

    (a) area =   1.6667       (b) area =   2.5000       (c) area =   6

     (e) area =   0                     total area = 10.1667

     

     

    Outside to C.G.             (H)                  3.444

    Inside to C.G.                (K)                  1.369

    Moment of Inertia                                 37.228

    Sect. Mod. Inside                                 27.197

    Sect. Mod. Outside                              10.811

    Horiz. Shear at Insul.    (Inside) 3.1 P.S.I.   <   50 P.S.I.    O.K.

    Horiz. Shear at Insul.    (Outside)          3.2 P.S.I.   <   50 P.S.I.    O.K.

     

     


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph / Fax (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 8/11/2004                                                           Page 16 of 21

    Project:     9ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

     

    ROOF BEAM - Stress And Deflection Between Studs

     

    Beam Used - See page 15

    Sxx =        10.811       Outside

    Sxx =        27.197        Inside

    Ixx  =          208.0

    Fiberglass min. strength =          31,300

     

     

    Span    =          24"       =          2 Ft.

     

    Allow. Def. = Span /    240                   0.10"

     

    Live Load         =          320

    Dead Load       =            20

    Total Load       =          340

     

    Fiberglass Stress           =          94 P.S.I.

    SF        =          332 O.K.

    Wood Stress    =          38 P.S.I.         <1400 P.S.I. O.K.

     

    Def.    =           0.0002"            <.10 ~ O.K.

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    std12


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph./Fax. (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date:  8/11/2004                                                          Page 17 of 21

    Project:  9 ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

     


    Typical Section Thru Wall

     

     

     

    a ~ 1.5 Oz. Per Sq. Ft. Fiberglass  >  Tensile Strength =           35,200          E = 2,000,000

    b ~ 1.5 Oz. Per Sq. Ft. Fiberglass  >  Tensile Strength =           35,200          E = 2,000,000                                                                 Comp. Strength  =        31,300

    c ~ Plywood   >   >   Allow. Stress = Min. 1500 p.s.i.   U.B.C.  2- 874      E = 1,800,000

    d ~ 2.5 Lb./Cu. ft. Urethane Foam   >  Shear Strength  =          50 p.s.i.         E = 1885

    e ~ 2.5" Deep Metal Stud                   > Yield Strength   =        33,000 p.s.i.  E = 29000000

    at 24" O/C                                           Wt. =   0.63 lbs/ft

    Gross Area =   0.184 sq. in.

       Net Area =    0.132 sq. in.

    lxx =     0.182 in. 4

     


     

     

     

     

     

     

     

     

     

     

     

     

    std 17


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph./Fax. (330) 525-7648

    jwagner@alliancelink.com

     

     

    By: JWW                     Date: 8/11/2004                                                           Page 18 of 21

    Project:  9 ft. High x 10 ft. Wide x 24 ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

    Wall Composite Section At Stud ~ Neglecting insulation


     

               


     


    Inside Fiberglass Thickness                   (A)       0.0625

    Outside Fiberglass Thickness                (B)         0.125

    Inside / Inside Wall                   (C)                4     

    Stud Depth                              (D)             2.5            

    Plywood Thickness                   (E)             0.5

    Width of Section                       (F)              12

    Total Depth                              (M)      4.1875

    Vertical Shear Load                                               189 ~ Pg. 19

     


     


    Properties ~ Converting To Composite Section      

    (a & b) n = 1.111         (e) n = 16.111              Effective Width (G) = 13.333

    (a) area =   0.8333       (b) area =   1.6667       (c) area =   6

     (e) area =   2.1267                        total area = 10.6267

     

     

    Outside to C.G.            (H)                     3.009

    Inside to C.G.               (K)                     1.179

    Moment of Inertia                                 21.103

    Sect. Mod. Inside                                 17.903

    Sect. Mod. Outside                                7.014

    Horiz. Shear at Insul.    (Inside) 4.577 P.S.I.   <   50 P.S.I.    O.K.

    Horiz. Shear at Insul.    (Outside)          3.665 P.S.I.   <   50 P.S.I.    O.K.


     

     

     

     

    std 17


                                                    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph/Fax. (330) 525-7648

    jwagner@alliancelink.com

     

     


    By: JWW                     Date: 8/11/2004                                                           Page 19 of 21

    Project:     9 ft. High x 10 ft. Wide x 24 ft Lg. Std. Bldg

    Customer: Plaschem Supply & Consulting Inc.

     


    Side Wall With Wind Load

                                                                           

                                                                Wind Pressure              =          42 psf ~ Pg.1

                                                                Wall Stud Spacing        =          2 ft ~ Pg.17

                                                                                                    H         =          9 ft

                                                               

                                                                From Pg. 18

                                                                Sect. Mod. Inside         =          17.9

                                                                Sect. Mod. Outside      =            7.0

                                                   

                                                    Uniform Wind Load On 2 ft. Wide Sect.           =          378

                                                   

                                                    Treated As A Cantelever Beam With Uniform Load


     


                                                                Max. Fiberglass Stress  =          2916    psi ~ OK

                                                                Max. Wood Stress                   =          1140    psi ~ OK

     


                                       

     

     

     

                                                    Treated As A Simple Beam With Uniform Load


                           

     

                                                                Max. Fiberglass Stress  =          1458    psi ~ OK

                                                                Max. Wood Stress                   =            570    psi ~ OK

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    std 19


    WAGNER ENGINEERING

    25725 Mountz Rd.

    Minerva, Oh 44657

    Ph./Fax. (330) 525-7648

    jwagner@alliancelink.com

     

     


    By: JWW                     Date: 8/11/2004                                                           Page 20 of 21

    Project:  9 ft. High x 10 ft. Wide x 24 ft Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     


    Side Wall With Seismic and 20% Snow Load

     


                Snow load                    =          160 psf ~ Pg. 1

                Dead Load                   =          10 psf

                Seismic coef.                =          0.277 ~ Pg. 1 2 ft

                Roof Stud Spacing        =          2 ft

                Roof area                     =          20 sq. ft

                Sect. Mod. Inside         =          17.9 ~ Pg. 18

                Sect. Mod. Outside      =          7 ~ Pg.18

                Total area                     =          10.6 ~ Pg.18

     

     

     

     



                                        H         =          105”

                                        W        =          420#

                                                                                   V        =           116#

     

     

     

     


                                                                1745 ~ Max. Fiberglass Bending Stress ~ OK

                                                                  682 ~ Max. Wood Bending Stress ~ OK

                                                                    40 ~ Comp. Stress ~ OK

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    std20

     


    WAGNER ENGINEERING

    25725 Mountz Rd.

     Minerva, Oh 44657

    Ph./Fax. (330) 525-7648

    jwagner@alliancelink.com

     

     

     

    By:  JWW                    Date:    8/11/2004                                                        Page 21 of 21

    Project:     9 Ft. High x 10 Ft. Wide x 24 Ft. Lg. Std. Bldg.

    Customer: Plaschem Supply & Consulting Inc.

     

     

    Building Overturning and Hold Downs

     

                            A         =             10 ft ~ Bldg. Width                            6000 # ~ Bldg. wt.

                            B          =               8 ft ~ Skid.Width                                   0 # ~ Equip.wt.

                            C         =               9 ft ~ Bldg. ht.                                 1000 # ~ Skid wt.

                            D         =          9.67 ft ~ Bldg. & Skid ht.

                                                       24 ft ~ Bldg. Length

     

    Wind Pressure  =                      42 PSF ~ Pg. 1

     

    40,824 ~ Overturning moment at top of skid

    24,000 ~ Resisting moment

        0.59 ~ Safety factor < 2.0 ~ Unsatisfactory

      7,206 ~ Minimum pounds req'd at top of skid for a S.F. of 2.0

                ~ Use minimum of (4) 1/2" dia. A307 bolts each side at top of skid.

     

    47,128 ~ Overturning moment at bottom of skid

    28,000 ~ Resisting moment

        0.59 ~ Safety factor < 2.0 ~ Unsatisfactory

      8,282 ~ Minimum pounds req'd at top of skid for a S.F. of 2.0

                ~ Use a minimum of (4) 1/2" dia. anchor bolts on each side at bottom of skid

                with 3 1/2" embed in concrete or equiv. earth anchor.

     

     

    std21

    CLICK HERE TO DOWNLOAD THIS DOCUMENT